BESCORE

BSC-CS3-2500K4600K

Grid-Scale DC Block 20 ft container

Updated Sep 21, 2026

Grid-Scale DC Block 20 ft container Updated Sep 21, 2026

Utility-scale BSC-CS3-2500K4600K is a containerized LFP battery energy storage system supplied as a DC block with 4.598 MWh nominal energy. It uses liquid cooling and contains 314 Ah prismatic cells. Its DC window spans 1081.6 to 1497.6 V, and it weighs 41.2 tonnes (90,830 lb).

Use Cases

The specifications of BSC-CS3-2500K4600K suggest use in front of the meter, connected to the utility network itself. By energy capacity, it belongs to the utility-scale class.

Capabilities

For BSC-CS3-2500K4600K, the specifications suggest peak shaving, discharging into the hours of highest demand, and grid services, support that helps operators run the electricity network. It is rated at 0.5P. Its DC block connects through a separate inverter, which points to renewable colocation, storing output from a wind or solar plant on the same site.

Nominal energy

4.6 MWh

C / P rate

0.5 P

What does this system typically cost?

BESSBASE.com user price estimates for BSC-CS3-2500K4600K by BESCORE and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for BSC-CS3-2500K4600K by BESCORE and similar systems across 20+ international markets.

Energy & Power

Nominal energy
4.6 MWh
C / P rate
0.5 P

Architecture

Container count
1
Installation
Outdoor-capable

DC Side

Nominal DC voltage
1,331.2 V
DC voltage range
1,081.6 – 1,497.6 V

AC Side

Physical & Footprint

Dimensions (W × D × H)
6,058 × 2,438 × 2,896 mm
Weight
41.2 t

Battery Cells

Chemistry
LFP
Cell capacity
314 Ah
Cell format
Prismatic
Cell supplier
CALB Group Co., Ltd., SVOLT Energy Technology Co., Ltd.

Lifespan

Protection

Ingress protection (IP)
IP55 IP67
Corrosion protection
C5
Fire & safety
Aerosol + water fire protection

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
typical default
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 % 100 %
1.216 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
101.7m² total site area · 1 × 1
1,095 ft²0.0102 ha0.025 acres22.1 m² / MWh238 ft² / MWh
Unit W × D
6.06 × 2.44 m
19.88 × 8 ft
Site envelope
12.06 × 8.44 m
39.56 × 27.68 ft
Per unit
101.7 m²
Installed energy
4.6 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More BESCORE Systems

14
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
BESCORE
BSC-CS3-2500K5000K DC Block · 20 ft container
5.02 MWh— — 0.5CLFP 314 Ah · Prismatic
BESCORE
BSC-CS3-2500K4600K DC Block · 20 ft container
4.6 MWh— — 0.5CLFP 314 Ah · Prismatic
BESCORE
BSC-CS3-2500K4000K DC Block · 20 ft container
4.18 MWh— — 0.5CLFP 314 Ah · Prismatic
BESCORE
BSC-CS3-2000K3700K DC Block · 20 ft container
3.76 MWh— — 0.5CLFP 314 Ah · Prismatic
BESCORE
BSC-CS3-2000K3300K DC Block · 20 ft container
3.34 MWh— — 0.5CLFP 314 Ah · Prismatic
BESCORE
BSC-CB4-0125K0261K AC Block · cabinet
0.26 MWh0.13 MW AC— 0.5CLFP 314 Ah · Prismatic
BESCORE
BSC-CE2-0105K0215K-M2B0S AC Block · cabinet
0.22 MWh0.11 MW AC— 0.5CLFP 280 Ah · Prismatic
BESCORE
BSC-CE2-0105K0215K-M4B0S AC Block · cabinet
0.22 MWh0.11 MW AC— 0.5CLFP 280 Ah · Prismatic
BESCORE
BSC-CE2-0105K0215K AC Block · cabinet
0.22 MWh0.11 MW AC— 0.5CLFP 280 Ah · Prismatic
BESCORE
BSC-CE2-0105K0200K-M2B0S AC Block · cabinet
0.2 MWh0.1 MW AC— 0.5CLFP 280 Ah · Prismatic
BESCORE
BSC-CE2-0105K0200K AC Block · cabinet
0.2 MWh0.1 MW AC— 0.5CLFP 280 Ah · Prismatic
BESCORE
BSC-CF2-0050K0100K-H AC Block · cabinet
0.1 MWh0.05 MW AC— LFP 280 Ah · Prismatic

About the Vendor

BESCORE Tier-2 Private Company

Founded in 2020, BESCORE makes battery energy storage systems for residential, commercial, industrial, outdoor, and community use. It operates through BESCORE Energie GmbH in Stuttgart, Germany, and BESCORE New Energy Technology (Qingdao) Co., Ltd. in Qingdao, China, and it covers the full BESS R&D, production, and sales chain with systems built around independent battery management, energy management, and power conversion systems.

Production scale 0.2-1 GWh
Company size Small (1-300)
Vertical integration Medium
Bankability Neutral

How to Read the Product Page

This profile of BSC-CS3-2500K4600K by BESCORE is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error

BESSBASE

Your trusted database of battery energy storage systems

  • X
  • LinkedIn

© 2026 BESSBASE.com by BESSBASE LLC. All rights reserved.