CLOU

CLC20-1000

Grid-Scale DC Block 20 ft container

Updated Aug 27, 2026

Grid-Scale DC Block 20 ft container Updated Aug 27, 2026

CLOU CLC20-1000 is an LFP battery energy storage system supplied as a DC block. It provides 2.2 MWh nominal energy with about a 2-hour duration. The unit uses air cooling.

Use Cases

Use in front of the meter, directly on the electricity network, is consistent with the specifications of CLOU CLC20-1000. Its energy capacity is within the utility-scale range.

Capabilities

A DC block that connects through a separate inverter makes CLOU CLC20-1000 a candidate for renewable colocation, sitting next to a wind or solar plant and sharing its grid connection. Its shortest listed configuration is 2 h, which points to peak shaving, discharging into the hours of highest demand. The specifications suggest grid services, support for the operation of the electricity network, and that 2 h listing indicates capacity value, being counted on as supply when the network is tight.

Nominal energy

2.2 MWh

Duration

2 hour

C / P rate

0.5 C

What does this system typically cost?

BESSBASE.com user price estimates for CLC20-1000 by CLOU and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for CLC20-1000 by CLOU and similar systems across 20+ international markets.

Energy & Power

Nominal energy
2.2 MWh
Duration
2 hour
C / P rate
0.5 C

Architecture

Container count
1
Installation
Outdoor-capable

DC Side

AC Side

Physical & Footprint

Dimensions (W × D × H)
6,100 × 2,440 × 2,590 mm

Battery Cells

Chemistry
LFP
Cell supplier
CLOU (in-house)

Lifespan

Protection

Ingress protection (IP)
IP54
Fire & safety
fire alarm, gas extinguishing system

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 2 h
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 % 100 %
1.216 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
102.1m² total site area · 1 × 1
1,099 ft²0.0102 ha0.025 acres46.4 m² / MWh500 ft² / MWh
Unit W × D
6.1 × 2.44 m
20.01 × 8.01 ft
Site envelope
12.1 × 8.44 m
39.7 × 27.69 ft
Per unit
102.1 m²
Installed energy
2.2 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More CLOU Systems

2
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
CLOU
CLC40-2500 DC Block · 40 ft container
5 MWh2.5 MW DC2 h 0.5CLFP
CLOU
CLC20-1000 DC Block · 20 ft container
2.2 MWh— 2 h 0.5CLFP

About the Vendor

CLOU Tier-1 Listed Company

Founded in 1996 and based in Shenzhen, China, CLOU, a Midea Group company, makes energy storage systems, power conversion systems, and related energy technology. By Q4 2024, it had delivered 6 GWh of energy storage systems for projects in the Americas, Chile, and Europe, and it designed its Yichun manufacturing base for 8 GWh of annual production capacity, including 3 GWh in the first phase.

Production scale 0.2-1 GWh
Company size Large (1000-10000)
Vertical integration Medium
Bankability Neutral

How to Read the Product Page

This profile of CLC20-1000 by CLOU is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error