CATL

EnerONE 1P416S

Industrial & Commercial DC Block

Updated Sep 11, 2026

Industrial & Commercial DC Block Updated Sep 11, 2026

CATL EnerONE 1P416S is an LFP battery energy storage system for commercial and industrial use with 407.3 kWh nominal energy. It is supplied as a DC block with liquid cooling and 306 Ah prismatic cells. It weighs 3.65 tonnes (8,047 lb).

Use Cases

The specifications of CATL EnerONE 1P416S suggest use behind the meter inside a customer's own electrical installation. Its nominal energy places it in the commercial and industrial size class.

Capabilities

The specifications suggest renewable colocation, storing output from a wind or solar plant on the same site, for CATL EnerONE 1P416S. Its DC block connects through a separate inverter.

Nominal energy

0.41 MWh

What does this system typically cost?

BESSBASE.com user price estimates for EnerONE 1P416S by CATL and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for EnerONE 1P416S by CATL and similar systems across 20+ international markets.

Energy & Power

Nominal energy
0.41 MWh

Architecture

Installation
Outdoor-capable

DC Side

Nominal DC voltage
1,331.2 V

AC Side

Physical & Footprint

Dimensions (W × D × H)
1,344 × 1,390 × 2,344 mm
Weight
3.65 t

Battery Cells

Chemistry
LFP
Cell capacity
306 Ah
Cell format
Prismatic
Cell supplier
CATL (in-house)

Lifespan

Design life
20 years

Protection

Ingress protection (IP)
IP66
Corrosion protection
C5
Fire & safety
UL9540A module/rack level, alternative fire suppression, deflagration venting optional, dry pipe optional, NFPA68 compliant

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
typical default
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 % 100 %
1.216 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
54.3m² total site area · 1 × 1
584 ft²0.0054 ha0.013 acres132.4 m² / MWh1,425 ft² / MWh
Unit W × D
1.34 × 1.39 m
4.41 × 4.56 ft
Site envelope
7.34 × 7.39 m
24.09 × 24.25 ft
Per unit
54.3 m²
Installed energy
0.41 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More CATL Systems

5
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
CATL30 MWh— 1–8 h flexNFPP
CATL4.07 MWh— — LFP 306 Ah · Prismatic
CATL
EnerC 10P416S (280Ah) DC Block · 20 ft container
3.72 MWh— — LFP 280 Ah · Prismatic
CATL
EnerONE 1P416S DC Block · cabinet
0.41 MWh— — LFP 306 Ah · Prismatic
CATL
EnerONE 1P416S DC Block · cabinet
0.38 MWh— — LFP 285 Ah · Prismatic

About the Vendor

CATL Tier-1 Listed Company

Contemporary Amperex Technology Co. Limited, founded in 2011, is based in Ningde, Fujian, China. The ATL founding team started CATL to expand from consumer lithium-ion batteries into broader energy uses, and the company now supplies batteries for energy storage projects worldwide, ranks first in BESS battery deliveries for five straight years, has deployed systems across about 2,300 energy storage projects, and expects cumulative shipments of 1 GWh of sodium-ion energy storage systems by the end of 2026.

Production scale 20+ GWh
Company size Major (10000+)
Vertical integration High
Bankability Overall Positive

How to Read the Product Page

This profile of EnerONE 1P416S by CATL is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error