LUNA2000-2.0MWH-1H1

Grid-Scale DC Block 20 ft container

Updated Aug 28, 2026

Grid-Scale DC Block 20 ft container Updated Aug 28, 2026

Huawei LUNA2000-2.0MWH-1H1 is a DC block battery energy storage system with 2.032 MWh nominal energy and 2.032 MW rated DC power, delivering about 1-hour duration. It uses air cooling, weighs 30 tonnes (66,139 lb), and operates across a 1250 to 1500 V DC window.

Use Cases

Use in front of the meter is consistent with the specifications of Huawei LUNA2000-2.0MWH-1H1. Its energy capacity is within the utility-scale range, and its supported protocols include IEC 104, used in utility control systems.

Capabilities

A configuration listed at 1 h as the shortest makes Huawei LUNA2000-2.0MWH-1H1 a candidate for peak shaving, reducing the peak load at the connection point, and points to grid services, work that helps keep the electricity network running. Its DC block connects through a separate inverter. That configuration suggests renewable colocation, sitting next to a wind or solar plant and sharing its grid connection.

Nominal energy

2.03 MWh

Rated DC power

2.03 MW

Duration

1 hour

C / P rate

1 C

What does this system typically cost?

BESSBASE.com user price estimates for LUNA2000-2.0MWH-1H1 by Huawei and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for LUNA2000-2.0MWH-1H1 by Huawei and similar systems across 20+ international markets.

Energy & Power

Nominal energy
2.03 MWh
Rated DC power
2.03 MW
Duration
1 hour
C / P rate
1 C

Architecture

Container count
1
Installation
Outdoor-capable

DC Side

Nominal DC voltage
1,250 V
DC voltage range
1,250 – 1,500 V

AC Side

Physical & Footprint

Dimensions (W × D × H)
6,058 × 2,438 × 2,896 mm
Weight
30 t

Battery Cells

Lifespan

Protection

Ingress protection (IP)
IP55
Corrosion protection
C5-Medium
Fire & safety
FM-200 / Novec 1230™

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 1 h
1C
—
State of health
new system
as-new
—
DC block
typical @1 h
round trip @ 1 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 % 100 %
1.216 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
101.7m² total site area · 1 × 1
1,095 ft²0.0102 ha0.025 acres50.1 m² / MWh539 ft² / MWh
Unit W × D
6.06 × 2.44 m
19.88 × 8 ft
Site envelope
12.06 × 8.44 m
39.56 × 27.68 ft
Per unit
101.7 m²
Installed energy
2.03 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Huawei Systems

8
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Huawei4.47 MWh2.24 MW DC— 0.5CLFP 280 Ah · Prismatic
Huawei
LUNA2000-2.0MWH-1H0 DC Block · 20 ft container
2.06 MWh2.06 MW DC1 h 1C—
Huawei
LUNA2000-2.0MWH-2H1 DC Block · 20 ft container
2.03 MWh1.02 MW DC2 h 0.5C—
Huawei
LUNA2000-2.0MWH-1H1 DC Block · 20 ft container
2.03 MWh2.03 MW DC1 h 1C—
Huawei
LUNA2000-200KWH-2H1 DC Block · cabinet
0.19 MWh— — —
Huawei
LUNA2000-161KWH-2H1 DC Block · cabinet
0.16 MWh— — —
Huawei
LUNA2000-129KWH-2H1 DC Block · cabinet
0.13 MWh— — —
Huawei
LUNA2000-97KWH-1H1 DC Block · cabinet
0.1 MWh— — —

About the Vendor

Huawei Tier-1 Private Company

Huawei, based in Shenzhen, China, provides solar and energy storage systems. The company has spent a decade developing its Smart String Grid-Forming ESS for utility-scale use, and the platform supports the 1.3 GWh battery energy storage system at Saudi Arabia’s Red Sea destination.

Production scale 2-20 GWh
Company size Major (10000+)
Vertical integration Medium
Bankability Neutral

How to Read the Product Page

This profile of LUNA2000-2.0MWH-1H1 by Huawei is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error