Pomega

PBQ20-416-0.5C

Grid-Scale DC Block

Updated Aug 28, 2026

Grid-Scale DC Block Updated Aug 28, 2026

Pomega PBQ20-416-0.5C is an LFP battery energy storage system supplied as a DC block for utility-scale use, with 5.01 MWh nominal energy. It uses liquid cooling and weighs 45 tonnes (99,208 lb) in total.

Use Cases

Use in front of the meter, directly on the electricity network, is consistent with the specifications of Pomega PBQ20-416-0.5C. Its nominal energy places it in the utility-scale size class.

Capabilities

Its DC block connects through a separate inverter points to renewable colocation, operating alongside a wind or solar plant on one site in Pomega PBQ20-416-0.5C.

Nominal energy

5.01 MWh

What does this system typically cost?

BESSBASE.com user price estimates for PBQ20-416-0.5C by Pomega and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for PBQ20-416-0.5C by Pomega and similar systems across 20+ international markets.

Energy & Power

Nominal energy
5.01 MWh

Architecture

Installation
Outdoor-capable

DC Side

AC Side

Physical & Footprint

Dimensions (W × D × H)
6,800 × 2,438 × 2,896 mm
Weight
45 t

Battery Cells

Chemistry
LFP
Cell supplier
Pomega (in-house)

Lifespan

Cycle life
≥ 9,000 cycles

Protection

Ingress protection (IP)
IP54
Fire & safety
Aerosol automatic fire protection, water mist

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
typical default
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 % 100 %
1.216 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
108m² total site area · 1 × 1
1,163 ft²0.0108 ha0.027 acres21.6 m² / MWh232 ft² / MWh
Unit W × D
6.8 × 2.44 m
22.31 × 8 ft
Site envelope
12.8 × 8.44 m
41.99 × 27.68 ft
Per unit
108 m²
Installed energy
5.01 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Pomega Systems

9
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Pomega
PBQ20-416-0.5C DC Block · cabinet
5.01 MWh— — LFP
Pomega
PBQ20-416-1C DC Block · cabinet
4.05 MWh— — LFP
Pomega
POD-L400 PRO DC Block · cabinet
0.4 MWh— — 1CLFP 304 Ah · Prismatic
Pomega
PHBRT-W-300 AC Block
0.31 MWh0.1 MW AC— LFP
Pomega
PHBRT-W-200 AC Block
0.31 MWh— — LFP
Pomega
POD-A230 DC Block · cabinet
0.23 MWh— — 1CLFP 100 Ah · Prismatic
Pomega
PHBRT-W-100 AC Block
0.2 MWh— — LFP
Pomega
POD-A100 DC Block · cabinet
0.1 MWh— — 1CLFP 100 Ah · Prismatic
Pomega
PHBRT-100 AC Block
0.1 MWh— — LFP

About the Vendor

Pomega Tier-2 Listed Company

Founded in 2023 and based in Ankara, Turkey, Pomega is a Kontrolmatik subsidiary that makes lithium-ion LFP battery cells, modules, and turnkey BESS. The company commissioned its 100,000-square-meter gigafactory in Polatlı in 2023 with annual capacity of 3 GWh and a plan to reach 6 GWh, and it calls the site Turkey’s first private-sector lithium-ion battery cell factory.

Production scale 2-20 GWh
Company size Small (1-300)
Vertical integration High
Bankability Neutral

How to Read the Product Page

This profile of PBQ20-416-0.5C by Pomega is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error

BESSBASE

BESSBASE is a screening intelligence platform used by asset owners, developers, and banks to assess industrial and grid-scale battery storage solutions.

  • X
  • LinkedIn

© 2026 BESSBASE.com by BESSBASE LLC. All rights reserved.