Alfen

TheBattery Elements

Industrial & Commercial DC Block

Updated Aug 28, 2026

Industrial & Commercial DC Block Updated Aug 28, 2026

Alfen TheBattery Elements is an LFP system for commercial and industrial use, supplied as a DC block with 372.7 kWh nominal energy and 1 and 6 hour configurations. It uses liquid cooling or forced air and water cooling, and weighs 3.5 tonnes (7,716 lb).

Use Cases

The specifications of Alfen TheBattery Elements suggest use behind the meter inside a customer's own electrical installation. Its energy capacity is within the commercial and industrial range.

Capabilities

For Alfen TheBattery Elements, the specifications suggest capacity value, standing in as firm capacity when demand peaks. Its longest listed configuration is 6 h. Its DC block connects through a separate inverter, which points to renewable colocation, operating alongside a wind or solar plant on one site. Its shortest listed configuration is 1 h, which points to peak shaving, cutting the power drawn from the grid at peak times.

Nominal energy

0.37 MWh

Duration

1–6 flexible

What does this system typically cost?

BESSBASE.com user price estimates for TheBattery Elements by Alfen and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for TheBattery Elements by Alfen and similar systems across 20+ international markets.

Energy & Power

Nominal energy
0.37 MWh
Duration
1–6 hour flexible

Architecture

Installation
Outdoor-capable

DC Side

AC Side

AC voltage parameters
3P + PEN
Grid frequency
50 Hz / 60 Hz

Physical & Footprint

Dimensions (W × D × H)
1,300 × 1,300 × 2,280 mm
Weight
3.5 t

Battery Cells

Chemistry
LFP
Cell supplier
CATL

Lifespan

Design life
10 years

Protection

Ingress protection (IP)
IP56 IP65 IP55
Corrosion protection
C4
Fire & safety
fire extinguishing, temperature management

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 1 h
1C
—
State of health
new system
as-new
—
DC block
typical @1 h
round trip @ 1 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 % 100 %
1.216 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
53.3m² total site area · 1 × 1
574 ft²0.0053 ha0.013 acres144 m² / MWh1,550 ft² / MWh
Unit W × D
1.3 × 1.3 m
4.27 × 4.27 ft
Site envelope
7.3 × 7.3 m
23.95 × 23.95 ft
Per unit
53.3 m²
Installed energy
0.37 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Alfen Systems

4
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Alfen
TB-MX-720 AC Block · 10 ft container
0.72 MWh0.27 MW AC— LFP 280 Ah · Prismatic
Alfen
TB-MX-540 AC Block · 10 ft container
0.54 MWh0.27 MW AC— LFP 280 Ah · Prismatic
Alfen
TheBattery Elements DC Block · cabinet
0.37 MWh— 1–6 h flexLFP
Alfen
TB-MX-360 AC Block · 10 ft container
0.36 MWh0.27 MW AC— LFP 280 Ah · Prismatic

About the Vendor

Alfen Tier-2 Listed Company

Alfen, founded in 1937 and based in Almere, the Netherlands, has developed battery energy storage systems since 2011, and its track record includes more than 1.4 GWh deployed, including 314 mobile units across 11 European countries. This shows a documented operating history in utility-scale and mobile BESS.

Production scale 0.2-1 GWh
Company size Middle (300-1000)
Vertical integration Minimal
Bankability Overall Positive

How to Read the Product Page

This profile of TheBattery Elements by Alfen is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error

BESSBASE

BESSBASE is a screening intelligence platform used by asset owners, developers, and banks to assess industrial and grid-scale battery storage solutions.

  • X
  • LinkedIn

© 2026 BESSBASE.com by BESSBASE LLC. All rights reserved.