Fluence

2000 SERIES

Grid-Scale DC Block Containerized

Updated Aug 28, 2026

Grid-Scale DC Block Containerized Updated Aug 28, 2026

Fluence 2000 SERIES is a containerized battery energy storage system with 2.436 MWh nominal energy and 2, 4, 6 and 8 hour configurations. It is supplied as a DC block with liquid cooling and 3 Ah prismatic cells. The system weighs 22.4 tonnes (49,383 lb).

Use Cases

The specifications of Fluence 2000 SERIES together point to use in front of the meter. Its energy capacity is within the utility-scale range. Its supported protocols include DNP3, used in utility control systems.

Capabilities

For Fluence 2000 SERIES, the specifications suggest capacity value, standing in as firm capacity when demand peaks. A DC block connects through a separate inverter, making it a candidate for renewable colocation, sitting next to a wind or solar plant and sharing its grid connection. Its shortest listed configuration is 2 h, which indicates peak shaving, discharging into the hours of highest demand, and grid services, support for the operation of the electricity network. It lists configurations up to 8 h, which points to energy shifting, taking in power and returning it hours later.

Nominal energy

2.44 MWh

Duration

2–8 flexible

C / P rate

0.5 P

What does this system typically cost?

BESSBASE.com user price estimates for 2000 SERIES by Fluence and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for 2000 SERIES by Fluence and similar systems across 20+ international markets.

Energy & Power

Nominal energy
2.44 MWh
Duration
2–8 hour flexible
C / P rate
0.5 P

Architecture

Installation
Outdoor-capable

DC Side

AC Side

Grid frequency
50 Hz / 60 Hz
Auxiliary power
16.7 kW / 9.5 kW

Physical & Footprint

Dimensions (W × D × H)
7,537 × 1,734 × 2,550 mm
Weight
22.4 t

Battery Cells

Cell capacity
3 Ah
Cell format
Prismatic
Cell supplier
AESC, Northvolt

Lifespan

Protection

Ingress protection (IP)
IP55
Seismic rating
Compliant with IEEE693 High,Meets IBC/CBC per SDC D,Conforms to ASCE 7-10
Fire & safety
3 multi-detectors and 2 gas detectors for CO/smoke/heat/H2, Active ventilation vents, 6 deflagration panels, Chiller and HVAC System

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 2 h
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 % 100 %
1.216 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
104.7m² total site area · 1 × 1
1,127 ft²0.0105 ha0.026 acres42.9 m² / MWh462 ft² / MWh
Unit W × D
7.54 × 1.73 m
24.73 × 5.69 ft
Site envelope
13.54 × 7.73 m
44.41 × 25.37 ft
Per unit
104.7 m²
Installed energy
2.44 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Fluence Systems

5
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Fluence
Gridstack DC Block · cabinet
— 2 MW AC1–6 h flexLFP
Fluence
Smartstack AC Block · cabinet
7.31 MWh— 2–8 h 0.5C · flex— 3 Ah · Prismatic
Fluence5.64 MWh— 2–8 h 0.25C · flex— 5 Ah · Prismatic
Fluence4.87 MWh— 2–8 h 0.5C · flex— 3 Ah · Prismatic
Fluence
2000 SERIES DC Block
2.44 MWh— 2–8 h 0.5C · flex— 3 Ah · Prismatic

About the Vendor

Fluence Tier-1 Listed Company

Fluence formed in 2017 as a joint venture between Siemens and AES and began operations in 2018. Based in Arlington, Virginia, it builds a business around grid-scale battery storage, services, and software, has more than 20 GWh of deployed and contracted storage systems worldwide, reported 52 GWh of energy storage across 48 markets, and in 2021 Fluence Energy, Inc. became the holding company and began trading on Nasdaq under FLNC.

Production scale 2-20 GWh
Company size Large (1000-10000)
Vertical integration Minimal
Bankability Neutral

How to Read the Product Page

This profile of 2000 SERIES by Fluence is assembled exclusively from public data to support early-stage screening and requires additional due diligence.