Fluence

Smartstack

Grid-ScaleAC Block

Updated Aug 28, 2026

Grid-ScaleAC BlockUpdated Aug 28, 2026

Fluence Smartstack is supplied as an AC block with 7.308 MWh nominal energy for 2, 4, 6 and 8 hour configurations. It uses liquid cooling and 3 Ah prismatic cells. The system weighs 10 tonnes (22,046 lb).

Use Cases

Fluence Smartstack has nominal energy in the utility-scale size class. Its supported protocols include DNP3, used in utility control systems, and the specifications indicate use in front of the meter.

Capabilities

Its longest listed configuration is 8 h, which points to capacity value, being counted on as supply when the network is tight. For Fluence Smartstack, the specifications suggest renewable colocation, operating alongside a wind or solar plant on one site: its AC block includes the inverter. Its shortest listed configuration is 2 h, which makes Fluence Smartstack a candidate for peak shaving, cutting the power drawn from the grid at peak times, and the specifications indicate grid services, support that helps operators run the electricity network. The specifications suggest energy shifting, taking in power and returning it hours later: it lists configurations up to 8 h.

Nominal energy

7.31MWh

Duration

2–8flexible

C / P rate

0.5P

What does this system typically cost?

BESSBASE.com user price estimates for Smartstack by Fluence and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for Smartstack by Fluence and similar systems across 20+ international markets.

Energy & Power

Nominal energy
7.31MWh
Duration
2–8 hourflexible
C / P rate
0.5 P

Architecture

Installation
Outdoor-capable

DC Side

AC Side

AC voltage
690 V
AC voltage parameters
3AC IT
Rated AC current
3762 A
Grid frequency
50 Hz / 60 Hz

Physical & Footprint

Dimensions (W × D × H)
7,369 × 2,200 × 1,584mm
Weight
10t

Battery Cells

Cell capacity
3 Ah
Cell format
Prismatic
Cell supplier
AESC, Northvolt

Lifespan

Protection

Enclosure protection
IP55
Corrosion protection
C5
Seismic rating
IEEE 693 moderate,IEEE 693 high,IBC,CBC,SDC D,ASCE 7-16
Fire & safety
deflagration testing, UL9540A fire testing, training

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 2 h
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 %100 %
1.216MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
109.6m² total site area · 1 × 1
1,180 ft²0.011 ha0.027 acres15 m² / MWh161 ft² / MWh
Unit W × D
7.37 × 2.2 m
24.18 × 7.22 ft
Site envelope
13.37 × 8.2 m
43.86 × 26.9 ft
Per unit
109.6 m²
Installed energy
7.31 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Fluence Systems

5
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Fluence
GridstackDC Block · cabinet
—2MWAC1–6hflexLFP
Fluence
SmartstackAC Block · cabinet
7.31MWh—2–8h0.5C · flex—3 Ah · Prismatic
Fluence5.64MWh—2–8h0.25C · flex—5 Ah · Prismatic
Fluence4.87MWh—2–8h0.5C · flex—3 Ah · Prismatic
Fluence
2000 SERIESDC Block
2.44MWh—2–8h0.5C · flex—3 Ah · Prismatic

About the Vendor

FluenceTier-1Listed Company

Fluence formed in 2017 as a joint venture between Siemens and AES and began operations in 2018. Based in Arlington, Virginia, it builds a business around grid-scale battery storage, services, and software, has more than 20 GWh of deployed and contracted storage systems worldwide, reported 52 GWh of energy storage across 48 markets, and in 2021 Fluence Energy, Inc. became the holding company and began trading on Nasdaq under FLNC.

Production scale2-20 GWh
Company sizeLarge (1000-10000)
Vertical integrationMinimal
BankabilityNeutral

How to Read the Product Page

This profile of Smartstack by Fluence is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

BESSBASE.COM

Your trusted database of battery energy storage systems

© 2026 BESSBASE.com. All rights reserved.