Ford Energy FE-450 is a containerized LFP battery energy storage system for utility-scale use, with 5.45 MWh nominal energy and about a 4-hour duration. It is a DC block with liquid cooling, 512 Ah prismatic cells, and a weight of 43.5 tonnes (95,901 lb).

Use Cases

Use in front of the meter, directly on the electricity network, is consistent with the specifications of Ford Energy FE-450. Its energy capacity is within the utility-scale range.

Capabilities

A listed 4 h configuration makes Ford Energy FE-450 a candidate for capacity value, counting as firm supply toward a network's peak needs. Its DC block connects through a separate inverter, which points to renewable colocation, operating alongside a wind or solar plant on one site. The specifications suggest energy shifting, storing charge and releasing it hours later.

Nominal energy

5.45MWh

Duration

4hour

C / P rate

0.25P

What does this system typically cost?

BESSBASE.com user price estimates for FE-450 by Ford Energy and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for FE-450 by Ford Energy and similar systems across 20+ international markets.

Energy & Power

Nominal energy
5.45MWh
Duration
4 hour
C / P rate
0.25 P

Architecture

Container count
1
Installation
Outdoor-capable

DC Side

DC voltage range
1,040 – 1,500 V

AC Side

Auxiliary power
37.5 kW

Physical & Footprint

Dimensions (W × D × H)
2,438 × 6,058 × 2,896mm
Weight
43.5t

Battery Cells

Chemistry
LFP
Cell capacity
512 Ah
Cell format
Prismatic Next-Gen 500+ Ah
Cell supplier
Ford Energy (in-house)

Lifespan

Protection

Enclosure protection
IP55
Corrosion protection
C5
Fire & safety
smoke detection, heat detection, hydrogen detection, ventilation, suppression

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 4 h
0.25C
—
State of health
new system
as-new
—
DC block
typical @4 h
round trip @ 4 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 %100 %
1.216MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
101.7m² total site area · 1 × 1
1,095 ft²0.0102 ha0.025 acres18.7 m² / MWh201 ft² / MWh
Unit W × D
2.44 × 6.06 m
8 × 19.88 ft
Site envelope
8.44 × 12.06 m
27.68 × 39.56 ft
Per unit
101.7 m²
Installed energy
5.45 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Ford Energy Systems

2
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Ford Energy
FE-450DC Block · 20 ft container
5.45MWh—4h0.25CLFP512 Ah · Prismatic Next-Gen 500+ Ah
Ford Energy
FE-250DC Block · 20 ft container
5.45MWh—2h0.5CLFP512 Ah · Prismatic Next-Gen 500+ Ah

About the Vendor

Ford EnergyTier-2Listed Company

Ford Energy, a wholly owned Ford Motor Company subsidiary introduced in 2026, focuses on U.S.-assembled battery energy storage systems for utilities, data centers, and large industrial and commercial customers. It is repurposing battery manufacturing capacity in Glendale, Kentucky, and plans to deploy at least 20 GWh a year, with first customer deliveries set for late 2027.

Production scale2-20 GWh
Company sizeSmall (1-300)
Vertical integrationHigh
BankabilityNeutral

How to Read the Product Page

This profile of FE-450 by Ford Energy is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

BESSBASE.COM

Your trusted database of battery energy storage systems

© 2026 BESSBASE.com. All rights reserved.