Tesvolt

IA-250kW/500kWh

Industrial & CommercialAC Block

Updated Aug 28, 2026

Industrial & CommercialAC BlockUpdated Aug 28, 2026

Tesvolt IA-250kW/500kWh is an LFP battery energy storage system for commercial and industrial applications, with 509 kWh nominal energy and 2, 4, 6 and 8 hour configurations. It is supplied as an AC block with air or liquid cooling and 244 kW rated DC power. The system uses 306 Ah prismatic cells and weighs 4.5 tonnes (9,921 lb).

Use Cases

Tesvolt IA-250kW/500kWh has nominal energy in the commercial and industrial size class. It connects at 400 V and is certified to low-voltage grid connection rules (EN50549-1). These specifications indicate use behind the meter.

Capabilities

Its AC block includes the inverter, which points to renewable colocation, storing output from a wind or solar plant on the same site. The shortest listed configuration is 2 h, and the specifications suggest peak shaving, reducing the peak load at the connection point. The longest listed configuration, 8 h, makes Tesvolt IA-250kW/500kWh a candidate for capacity value, counting as firm supply toward a network's peak needs.

Nominal energy

0.51MWh

Rated AC power

0.25MW

Rated DC power

0.24MW

Duration

2–8flexible

What does this system typically cost?

BESSBASE.com user price estimates for IA-250kW/500kWh by Tesvolt and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for IA-250kW/500kWh by Tesvolt and similar systems across 20+ international markets.

Energy & Power

Nominal energy
0.51MWh
Rated DC power
0.24MW
Rated AC power
0.25MW
Duration
2–8 hourflexible

Architecture

Installation
Outdoor-capable

DC Side

Nominal DC voltage
832 V
DC voltage range
728 – 936 V

AC Side

AC voltage
400 V
AC voltage parameters
3/N/PE
AC voltage range
360..440 V
Rated AC current
360.8 A
Grid frequency
50 Hz / 60 Hz

Physical & Footprint

Dimensions (W × D × H)
1,940 × 1,500 × 2,100mm
Weight
4.5t

Battery Cells

Chemistry
LFP
Cell capacity
306 Ah
Cell format
Prismatic
Cell supplier
Samsung SDI

Lifespan

Protection

Enclosure protection
IP55
Corrosion protection
C5
Fire & safety
Smoke Detector, Heat Detector, Alarm Sounder, Aerosol, Sprinkler, Optional: Flammable Gas Detector, Vent Plate

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 2 h
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 %100 %
1.216MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
59.6m² total site area · 1 × 1
641 ft²0.006 ha0.015 acres116.8 m² / MWh1,257 ft² / MWh
Unit W × D
1.94 × 1.5 m
6.36 × 4.92 ft
Site envelope
7.94 × 7.5 m
26.05 × 24.61 ft
Per unit
59.6 m²
Installed energy
0.51 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Tesvolt Systems

14
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Tesvolt
TESVOLT TALLONDC Block · 20 ft container
5.02MWh2.5MWDC2h0.5CLFP314 Ah · Prismatic
Tesvolt
IA-125kW/500kWhAC Block · cabinet
0.51MWh0.13MWAC2–8hflexLFP306 Ah · Prismatic
Tesvolt
IA-187kW/500kWhAC Block · cabinet
0.51MWh0.19MWAC2–8hflexLFP306 Ah · Prismatic
Tesvolt
IA-250kW/500kWhAC Block · cabinet
0.51MWh0.25MWAC2–8hflexLFP306 Ah · Prismatic
Tesvolt
IA-62.5kW/500kWhAC Block · cabinet
0.51MWh0.06MWAC2–8hflexLFP306 Ah · Prismatic
Tesvolt
TESVOLT FORTONAC Block · cabinet
0.09MWh0.09MWAC1h1CLFP
Tesvolt
TAYTAN/10-40DC Block · cabinet
0.06MWh0.06MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/09-40DC Block · cabinet
0.06MWh0.06MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/08-40DC Block · cabinet
0.05MWh0.05MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/06-40DC Block · cabinet
0.04MWh0.04MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/07-40DC Block · cabinet
0.04MWh0.04MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/05-40DC Block · cabinet
0.03MWh0.03MWDC1h1CLFP75 Ah · Prismatic

About the Vendor

TesvoltTier-2Listed Company

TESVOLT, founded in 2014, makes battery energy storage systems and integrates them from Lutherstadt Wittenberg, Germany. It has delivered more than 6,000 storage projects worldwide and reported 13.5 GWh of cumulative deployments, and its lithium-ion systems serve commercial, industrial, and utility-scale uses while the company expands its Wittenberg headquarters with a gigafactory designed for 4 GWh of annual production.

Production scale2-20 GWh
Company sizeSmall (1-300)
Vertical integrationMinimal
BankabilityNeutral

How to Read the Product Page

This profile of IA-250kW/500kWh by Tesvolt is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

BESSBASE.COM

Your trusted database of battery energy storage systems