Tesvolt

TESVOLT FORTON

Industrial & CommercialAC Block

Updated Aug 27, 2026

Industrial & CommercialAC BlockUpdated Aug 27, 2026

Tesvolt TESVOLT FORTON is an LFP battery energy storage system for commercial and industrial use, with 92 kWh nominal energy and about a 1-hour duration. It is supplied as an AC block with 92 kW rated DC power and air cooling. It records 98.7% AC and 98.5% DC round-trip efficiency and weighs 1.4 tonnes (3,086 lb).

Use Cases

Use behind the meter is consistent with the specifications of TESVOLT FORTON. By energy capacity, it belongs to the commercial and industrial class, and it connects at 400 V.

Capabilities

Its AC block includes the inverter, which points to TESVOLT FORTON for renewable colocation, sitting next to a wind or solar plant and sharing its grid connection. The listed configurations include 1 h as the minimum. That configuration points to peak shaving, discharging into the hours of highest demand.

Nominal energy

0.09MWh

Rated AC power

0.09MW

Rated DC power

0.09MW

Duration

1hour

C / P rate

1C

Round-trip efficiency (AC)

98.7 %AC

What does this system typically cost?

BESSBASE.com user price estimates for TESVOLT FORTON by Tesvolt and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for TESVOLT FORTON by Tesvolt and similar systems across 20+ international markets.

Energy & Power

Nominal energy
0.09MWh
Rated DC power
0.09MW
Rated AC power
0.09MW
Duration
1 hour
C / P rate
1 C
Round-trip efficiency (AC)
98.7 %
Round-trip efficiency (DC)
98.5 %

Architecture

Installation
Indoor or outdoor

DC Side

Nominal DC voltage
921.6 V
DC voltage range
806.4 – 1,036.8 V

AC Side

AC voltage
400 V
AC voltage parameters
three-phase
AC voltage range
300 - 580 V
Rated AC current
132.3 A
Grid frequency
50 Hz / 60 Hz

Physical & Footprint

Dimensions (W × D × H)
860 × 1,300 × 2,100mm
Weight
1.4t

Battery Cells

Chemistry
LFP
Cell supplier
Samsung SDI

Lifespan

Protection

Enclosure protection
IP55IP66NEMA 4X
Corrosion protection
C4

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 1 h
1C
—
State of health
new system
as-new
—
DC block
rte_dc 98.5 % @1 h
round trip @ 1 h
98.5 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.5 pts
Plant Round-Trip Efficiency at the Point of Interconnection
86.2 %
40 %100 %
1.161MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
50.1m² total site area · 1 × 1
539 ft²0.005 ha0.012 acres556.4 m² / MWh5,989 ft² / MWh
Unit W × D
0.86 × 1.3 m
2.82 × 4.27 ft
Site envelope
6.86 × 7.3 m
22.51 × 23.95 ft
Per unit
50.1 m²
Installed energy
0.09 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Tesvolt Systems

14
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Tesvolt
TESVOLT TALLONDC Block · 20 ft container
5.02MWh2.5MWDC2h0.5CLFP314 Ah · Prismatic
Tesvolt
IA-125kW/500kWhAC Block · cabinet
0.51MWh0.13MWAC2–8hflexLFP306 Ah · Prismatic
Tesvolt
IA-187kW/500kWhAC Block · cabinet
0.51MWh0.19MWAC2–8hflexLFP306 Ah · Prismatic
Tesvolt
IA-250kW/500kWhAC Block · cabinet
0.51MWh0.25MWAC2–8hflexLFP306 Ah · Prismatic
Tesvolt
IA-62.5kW/500kWhAC Block · cabinet
0.51MWh0.06MWAC2–8hflexLFP306 Ah · Prismatic
Tesvolt
TESVOLT FORTONAC Block · cabinet
0.09MWh0.09MWAC1h1CLFP
Tesvolt
TAYTAN/10-40DC Block · cabinet
0.06MWh0.06MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/09-40DC Block · cabinet
0.06MWh0.06MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/08-40DC Block · cabinet
0.05MWh0.05MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/06-40DC Block · cabinet
0.04MWh0.04MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/07-40DC Block · cabinet
0.04MWh0.04MWDC1h1CLFP75 Ah · Prismatic
Tesvolt
TAYTAN/05-40DC Block · cabinet
0.03MWh0.03MWDC1h1CLFP75 Ah · Prismatic

About the Vendor

TesvoltTier-2Listed Company

TESVOLT, founded in 2014, makes battery energy storage systems and integrates them from Lutherstadt Wittenberg, Germany. It has delivered more than 6,000 storage projects worldwide and reported 13.5 GWh of cumulative deployments, and its lithium-ion systems serve commercial, industrial, and utility-scale uses while the company expands its Wittenberg headquarters with a gigafactory designed for 4 GWh of annual production.

Production scale2-20 GWh
Company sizeSmall (1-300)
Vertical integrationMinimal
BankabilityNeutral

How to Read the Product Page

This profile of TESVOLT FORTON by Tesvolt is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

BESSBASE.COM

Your trusted database of battery energy storage systems

© 2026 BESSBASE.com. All rights reserved.