FENECON

INDUSTRIAL XL

Grid-Scale AC Block Containerized

Updated Aug 25, 2026

Grid-Scale AC Block Containerized Updated Aug 25, 2026

FENECON INDUSTRIAL XL is a containerized NMC battery energy storage system for utility-scale projects with 4.072 MWh nominal energy. It is supplied as an AC block with 1.5 MW rated DC power. The system uses water-glycol or HVAC cooling, delivers 95% DC round-trip efficiency, and weighs 32 tonnes (70,548 lb).

Use Cases

FENECON INDUSTRIAL XL belongs to the utility-scale class by energy capacity. That specification points to use in front of the meter, on the utility's side of the connection.

Capabilities

Its AC block includes the inverter, which points to renewable colocation, operating alongside a wind or solar plant on one site. FENECON INDUSTRIAL XL holds about 2.71 h of storage at full power, calculated from 4.072 MWh and 1.5 MW, and the specifications suggest capacity value, standing in as firm capacity when demand peaks.

Nominal energy

4.07 MWh

Rated AC power

1.5 MW

Rated DC power

1.5 MW

Round-trip efficiency (AC)

95 % DC

What does this system typically cost?

BESSBASE.com user price estimates for INDUSTRIAL XL by FENECON and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for INDUSTRIAL XL by FENECON and similar systems across 20+ international markets.

Energy & Power

Nominal energy
4.07 MWh
Rated DC power
1.5 MW
Rated AC power
1.5 MW
Round-trip efficiency (DC)
95 %

Architecture

DC Side

AC Side

AC voltage
400 V
AC voltage parameters
3L+PE
Grid frequency
50 Hz / 60 Hz

Physical & Footprint

Dimensions (W × D × H)
6,750 × 2,444 × 2,900 mm
Weight
32 t

Battery Cells

Chemistry
NMC
Cell supplier
CATL

Lifespan

Cycle life
8,000 cycles
Design life
10 years

Protection

Fire & safety
fire alarm system, optional aerosol-based fire suppression system, drip tray

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
energy ÷ power 2.71 h
0.37C
—
State of health
new system
as-new
—
DC block
rte_dc 95 % @2.7 h
round trip @ 2.7 h
95 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.4 pts
Plant Round-Trip Efficiency at the Point of Interconnection
83.1 %
40 % 100 %
1.203 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
107.7m² total site area · 1 × 1
1,159 ft²0.0108 ha0.027 acres26.5 m² / MWh285 ft² / MWh
Unit W × D
6.75 × 2.44 m
22.15 × 8.02 ft
Site envelope
12.75 × 8.44 m
41.83 × 27.7 ft
Per unit
107.7 m²
Installed energy
4.07 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More FENECON Systems

10
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
FENECON
INDUSTRIAL XL AC Block
4.07 MWh1.5 MW AC— NMC
FENECON
INDUSTRIAL L AC Block
1.29 MWh0.74 MW AC— NMC
FENECON1.05 MWh0.46 MW AC2.28 h 0.2CLFP
FENECON
INDUSTRIAL M AC Block
0.66 MWh0.7 MW AC— NMC
FENECON0.21 MWh0.09 MW AC2.28 h 0.2CLFP
FENECON0.17 MWh0.09 MW AC1.83 h 0.2C · flexLFP
FENECON
INDUSTRIAL S AC Block
0.16 MWh0.09 MW AC— NMC
FENECON
COMMERCIAL 92 AC Block · cabinet
0.08 MWh0.09 MW AC— LFP
FENECON
COMMERCIAL 50 AC Block · cabinet
0.05 MWh0.05 MW AC— LFP
FENECON0.04 MWh0.09 MW AC1.37 h 0.2CLFP

About the Vendor

FENECON Tier-2 Private Company

FENECON, founded in 2011 in Iggensbach, Lower Bavaria, is a German maker of battery storage systems based in Deggendorf, Germany. The company runs its production site in Iggensbach and has expanded to Vilshofen/Albersdorf and Deggendorf, and in 2021 it founded FERESTO GmbH to extend its battery storage work.

Production scale 0.2-1 GWh
Company size Small (1-300)
Vertical integration Minimal
Bankability Neutral

How to Read the Product Page

This profile of INDUSTRIAL XL by FENECON is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error

BESSBASE

BESSBASE is a screening intelligence platform used by asset owners, developers, and banks to assess industrial and grid-scale battery storage solutions.

  • X
  • LinkedIn

© 2026 BESSBASE.com by BESSBASE LLC. All rights reserved.