INTILION

INTILION | scalecube 4073-05C

Grid-ScaleDC Block20 ft container

Updated Aug 28, 2026

Grid-ScaleDC Block20 ft containerUpdated Aug 28, 2026

INTILION | scalecube 4073-05C is a containerized LFP battery energy storage system with 4.07347 MWh nominal energy. It is supplied as a DC block with liquid cooling and 306 Ah prismatic cells. The system weighs 36 tonnes (79,366 lb) and is rated for 50 Hz grids.

Use Cases

The specifications of INTILION | scalecube 4073-05C suggest use in front of the meter, connected to the utility network itself. Its energy capacity is within the utility-scale range.

Capabilities

INTILION | scalecube 4073-05C is rated at 0.5P, and the specifications suggest grid services, support for the operation of the electricity network. Its DC block connects through a separate inverter, which makes it a candidate for renewable colocation, sitting next to a wind or solar plant and sharing its grid connection. That rating points to peak shaving, reducing the peak load at the connection point.

Nominal energy

4.07MWh

C / P rate

0.5P

What does this system typically cost?

BESSBASE.com user price estimates for INTILION | scalecube 4073-05C by INTILION and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for INTILION | scalecube 4073-05C by INTILION and similar systems across 20+ international markets.

Energy & Power

Nominal energy
4.07MWh
C / P rate
0.5 P

Architecture

Container count
1
Installation
Outdoor-capable

DC Side

AC Side

AC voltage range
575 – 690V (+/- 10%)
Rated AC current
1,727 A
Grid frequency
50 Hz

Physical & Footprint

Dimensions (W × D × H)
2,438 × 6,058 × 2,896mm
Weight
36t

Battery Cells

Chemistry
LFP
Cell capacity
306 Ah
Cell format
Prismatic
Cell supplier
CATL

Lifespan

Design life
15 years

Protection

Enclosure protection
IP55
Corrosion protection
C5

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
typical default
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 %100 %
1.216MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
101.7m² total site area · 1 × 1
1,095 ft²0.0102 ha0.025 acres25 m² / MWh269 ft² / MWh
Unit W × D
2.44 × 6.06 m
8 × 19.88 ft
Site envelope
8.44 × 12.06 m
27.68 × 39.56 ft
Per unit
101.7 m²
Installed energy
4.07 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More INTILION Systems

8
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
INTILION
INTILION | scalecube 4073-05CDC Block · 20 ft container
4.07MWh——0.5CLFP306 Ah · Prismatic
INTILION
scalepac8AC Block · cabinet
2.03MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
scalepac7AC Block · cabinet
1.78MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
scalepac6AC Block · cabinet
1.52MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
scalepac5AC Block · cabinet
1.27MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
scalepac4AC Block · cabinet
1.02MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
INTILION | scalecube 407-05CDC Block · cabinet
0.41MWh——0.5CLFP306 Ah · Prismatic
INTILION
scalepacAC Block · cabinet
0.25MWh125MWAC—0.5CLFP306 Ah · Prismatic

About the Vendor

INTILIONTier-2Listed Company

Founded in 2019 as a spin-off from the HOPPECKE Group, INTILION put the group’s lithium-ion work into one company focused on stationary energy storage. Based in Paderborn, Germany, it supplies modular lithium-ion systems from 1 to about 100 MWh and works as an energy storage provider in the DACH region.

Production scale0.2-1 GWh
Company sizeSmall (1-300)
Vertical integrationMinimal
BankabilityNeutral

How to Read the Product Page

This profile of INTILION | scalecube 4073-05C by INTILION is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

BESSBASE.COM

Your trusted database of battery energy storage systems