INTILION scalepac8 is an LFP battery energy storage system with 2.032 MWh nominal energy and about a 2-hour duration. It is supplied as an AC block with air or liquid cooling and delivers 90% AC round-trip efficiency. The system uses 306 Ah prismatic cells and weighs 22.4 tonnes (49,383 lb).

Use Cases

The specifications of INTILION scalepac8 together point to use in front of the meter. Its energy capacity is within the utility-scale range. It is certified to medium- or high-voltage grid connection rules (VDE-AR-N 4110).

Capabilities

For INTILION scalepac8, the specifications suggest renewable colocation, operating alongside a wind or solar plant on one site, and its AC block includes the inverter. Its shortest listed configuration is 2 h. That configuration makes INTILION scalepac8 a candidate for peak shaving, cutting the power drawn from the grid at peak times; indicates grid services, support for the operation of the electricity network; and the specifications suggest capacity value, counting as firm supply toward a network's peak needs.

Nominal energy

2.03MWh

Duration

2hour

C / P rate

0.5P

Round-trip efficiency (AC)

90 %AC

What does this system typically cost?

BESSBASE.com user price estimates for scalepac8 by INTILION and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for scalepac8 by INTILION and similar systems across 20+ international markets.

Energy & Power

Nominal energy
2.03MWh
Duration
2 hour
C / P rate
0.5 P
Round-trip efficiency (AC)
90 %

Architecture

Installation
Outdoor-capable

DC Side

AC Side

AC voltage
400 V
AC voltage parameters
3L, N, PE
AC voltage range
-15% to +10%
Rated AC current
217 A

Physical & Footprint

Dimensions (W × D × H)
11,360 × 1,425 × 2,250mm
Weight
22.4t

Battery Cells

Chemistry
LFP
Cell capacity
306 Ah
Cell format
Prismatic
Cell supplier
CATL

Lifespan

Design life
15 years

Protection

Enclosure protection
IP54
Corrosion protection
C5

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 2 h
0.5C
—
State of health
new system
as-new
—
AC block (battery + PCS)
rte_ac 90 % @2 h
round trip @ 2 h
90 %
PCS (DC/AC)
Not Applicable for AC Block ESS
each way
—
—
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
81.1 %
40 %100 %
1.232MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
128.9m² total site area · 1 × 1
1,387 ft²0.0129 ha0.032 acres63.5 m² / MWh683 ft² / MWh
Unit W × D
11.36 × 1.43 m
37.27 × 4.68 ft
Site envelope
17.36 × 7.43 m
56.96 × 24.36 ft
Per unit
128.9 m²
Installed energy
2.03 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More INTILION Systems

8
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
INTILION
INTILION | scalecube 4073-05CDC Block · 20 ft container
4.07MWh——0.5CLFP306 Ah · Prismatic
INTILION
scalepac8AC Block · cabinet
2.03MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
scalepac7AC Block · cabinet
1.78MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
scalepac6AC Block · cabinet
1.52MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
scalepac5AC Block · cabinet
1.27MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
scalepac4AC Block · cabinet
1.02MWh—2h0.5CLFP306 Ah · Prismatic
INTILION
INTILION | scalecube 407-05CDC Block · cabinet
0.41MWh——0.5CLFP306 Ah · Prismatic
INTILION
scalepacAC Block · cabinet
0.25MWh125MWAC—0.5CLFP306 Ah · Prismatic

About the Vendor

INTILIONTier-2Listed Company

Founded in 2019 as a spin-off from the HOPPECKE Group, INTILION put the group’s lithium-ion work into one company focused on stationary energy storage. Based in Paderborn, Germany, it supplies modular lithium-ion systems from 1 to about 100 MWh and works as an energy storage provider in the DACH region.

Production scale0.2-1 GWh
Company sizeSmall (1-300)
Vertical integrationMinimal
BankabilityNeutral

How to Read the Product Page

This profile of scalepac8 by INTILION is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.