RCT Power

POWER CESS 4000

Grid-Scale DC Block 20 ft container

Updated Sep 17, 2026

Grid-Scale DC Block 20 ft container Updated Sep 17, 2026

Supplied as a containerized DC block, RCT Power POWER CESS 4000 is an LFP battery energy storage system with liquid cooling and 306 Ah prismatic cells. It stores 4.073 MWh of nominal energy. It supports 2 and 8 hour configurations.

Use Cases

RCT Power POWER CESS 4000 has an energy capacity within the utility-scale range. This specification points to use in front of the meter, on the utility's side of the connection.

Capabilities

RCT Power POWER CESS 4000 has a shortest listed configuration of 2 h, and that configuration indicates grid services, support for the operation of the electricity network, and peak shaving, cutting the power drawn from the grid at peak times. The specifications suggest energy shifting, taking in power and returning it hours later, and it lists configurations up to 8 h. Its longest listed configuration is 8 h, which makes it a candidate for capacity value, counting as firm supply toward a network's peak needs. Its DC block connects through a separate inverter, which points to renewable colocation, operating alongside a wind or solar plant on one site.

Nominal energy

4.07 MWh

Duration

2–8 flexible

C / P rate

0.1–0.5 C

What does this system typically cost?

BESSBASE.com user price estimates for POWER CESS 4000 by RCT Power and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for POWER CESS 4000 by RCT Power and similar systems across 20+ international markets.

Energy & Power

Nominal energy
4.07 MWh
Duration
2–8 hour flexible
C / P rate
0.1–0.5 C

Architecture

Container count
1
Installation
Outdoor-capable

DC Side

Nominal DC voltage
1,331.2 V
DC voltage range
1,164 – 1,498 V

AC Side

Physical & Footprint

Dimensions (W × D × H)
6,100 × 2,800 × 1,498 mm
Weight
38 t

Battery Cells

Chemistry
LFP
Cell capacity
306 Ah
Cell format
Prismatic
Cell supplier
RCT Power (in-house)

Lifespan

Protection

Ingress protection (IP)
IP55
Corrosion protection
C4 C5
Fire & safety
End-to-end fire protection architecture

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
duration 2 h
0.5C
—
State of health
new system
as-new
—
DC block
typical @2 h
round trip @ 2 h
94 %
PCS (DC/AC)
typical default
each way
97.02 %
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.3 pts
Plant Round-Trip Efficiency at the Point of Interconnection
82.2 %
40 % 100 %
1.216 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
106.5m² total site area · 1 × 1
1,146 ft²0.0106 ha0.026 acres26.2 m² / MWh282 ft² / MWh
Unit W × D
6.1 × 2.8 m
20.01 × 9.19 ft
Site envelope
12.1 × 8.8 m
39.7 × 28.87 ft
Per unit
106.5 m²
Installed energy
4.07 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More RCT Power Systems

8
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
RCT Power
POWER CESS 4000 DC Block · 20 ft container
4.07 MWh— 2–8 h 0.1–0.5C · flexLFP 306 Ah · Prismatic
RCT Power0.93 MWh0.5 MW AC— 0.5CLFP
RCT Power0.7 MWh0.38 MW AC— 0.5CLFP
RCT Power0.47 MWh0.25 MW AC— 0.5CLFP
RCT Power
POWER CESS 200 DC STS AC Block · cabinet
0.23 MWh0.1 MW AC— 0.5CLFP
RCT Power
POWER CESS 200 DC AC Block · cabinet
0.23 MWh0.1 MW AC— 0.5CLFP
RCT Power
POWER CESS 200 AC STS AC Block · cabinet
0.23 MWh0.1 MW AC— 0.5CLFP
RCT Power
POWER CESS 200 AC AC Block · cabinet
0.23 MWh0.1 MW AC— 0.5CLFP

About the Vendor

RCT Power Tier-2 Listed Company

RCT Power, founded in 2012 and based in Konstanz, Germany, makes battery storage systems. By August 2024, it had delivered more than 10 GWh of storage capacity, including 50 large systems to the United States, and it said it could make 25 GWh, with plans to expand to 40 GWh by the end of 2025.

Production scale 2-20 GWh
Company size Small (1-300)
Vertical integration Medium
Bankability Neutral

How to Read the Product Page

This profile of POWER CESS 4000 by RCT Power is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error