RCT Power

POWER CESS 700 AC

Industrial & Commercial AC Block Containerized

Updated Sep 17, 2026

Industrial & Commercial AC Block Containerized Updated Sep 17, 2026

699 kWh nominal energy, RCT Power POWER CESS 700 AC is a containerized LFP battery energy storage system for commercial and industrial use, supplied as an AC block. Liquid cooling supports 98.6% AC round-trip efficiency. It operates across a 715 to 928 V DC window and weighs 9.7 tonnes (21,385 lb).

Use Cases

The specifications of RCT Power POWER CESS 700 AC suggest use behind the meter inside a customer's own electrical installation. Its energy capacity is within the commercial and industrial range, and it connects at 230 V, a low-voltage AC connection.

Capabilities

For RCT Power POWER CESS 700 AC, the specifications suggest peak shaving, discharging into the hours of highest demand. It holds about 1.86 h of storage at full power, calculated from 699 kWh and 375 kW. Its AC block includes the inverter, which makes RCT Power POWER CESS 700 AC a candidate for renewable colocation, operating alongside a wind or solar plant on one site.

Nominal energy

0.7 MWh

Rated AC power

0.38 MW

C / P rate

0.5 C

Round-trip efficiency (AC)

98.6 % AC

What does this system typically cost?

BESSBASE.com user price estimates for POWER CESS 700 AC by RCT Power and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for POWER CESS 700 AC by RCT Power and similar systems across 20+ international markets.

Energy & Power

Nominal energy
0.7 MWh
Rated AC power
0.38 MW
C / P rate
0.5 C
Round-trip efficiency (AC)
98.6 %

Architecture

Installation
Outdoor-capable

DC Side

Nominal DC voltage
832 V
DC voltage range
715 – 928 V

AC Side

AC voltage
230 V
AC voltage parameters
L1, L2, L3, N, PE
Rated AC current
540 A
Grid frequency
50 Hz / 60 Hz

Physical & Footprint

Dimensions (W × D × H)
2,991 × 2,438 × 2,438 mm
Weight
9.7 t

Battery Cells

Chemistry
LFP
Cell supplier
RCT Power (in-house)

Lifespan

Cycle life
6,000 cycles
Cycle-life conditions
80% SOH

Protection

Ingress protection (IP)
IP54
Corrosion protection
C4 C5
Fire & safety
Detection and Extraction of Flammable and Explosive Gases, Smoke Sensor, Temperature Sensor, Aerosol, Audible and Visual Alarm, Dry Pipe and Sprinkler System, Emergency Stop

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
energy ÷ power 1.84 h
0.54C
—
State of health
new system
as-new
—
AC block (battery + PCS)
rte_ac 98.6 % @1.8 h
round trip @ 1.8 h
98.6 %
PCS (DC/AC)
Not Applicable for AC Block ESS
each way
—
—
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.7 pts
Plant Round-Trip Efficiency at the Point of Interconnection
88.9 %
40 % 100 %
1.125 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
75.9m² total site area · 1 × 1
817 ft²0.0076 ha0.019 acres108.4 m² / MWh1,167 ft² / MWh
Unit W × D
2.99 × 2.44 m
9.81 × 8 ft
Site envelope
8.99 × 8.44 m
29.5 × 27.68 ft
Per unit
75.9 m²
Installed energy
0.7 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More RCT Power Systems

8
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
RCT Power
POWER CESS 4000 DC Block · 20 ft container
4.07 MWh— 2–8 h 0.1–0.5C · flexLFP 306 Ah · Prismatic
RCT Power0.93 MWh0.5 MW AC— 0.5CLFP
RCT Power
POWER CESS 700 AC AC Block
0.7 MWh0.38 MW AC— 0.5CLFP
RCT Power0.47 MWh0.25 MW AC— 0.5CLFP
RCT Power
POWER CESS 200 DC STS AC Block · cabinet
0.23 MWh0.1 MW AC— 0.5CLFP
RCT Power
POWER CESS 200 DC AC Block · cabinet
0.23 MWh0.1 MW AC— 0.5CLFP
RCT Power
POWER CESS 200 AC STS AC Block · cabinet
0.23 MWh0.1 MW AC— 0.5CLFP
RCT Power
POWER CESS 200 AC AC Block · cabinet
0.23 MWh0.1 MW AC— 0.5CLFP

About the Vendor

RCT Power Tier-2 Listed Company

RCT Power, founded in 2012 and based in Konstanz, Germany, makes battery storage systems. By August 2024, it had delivered more than 10 GWh of storage capacity, including 50 large systems to the United States, and it said it could make 25 GWh, with plans to expand to 40 GWh by the end of 2025.

Production scale 2-20 GWh
Company size Small (1-300)
Vertical integration Medium
Bankability Neutral

How to Read the Product Page

This profile of POWER CESS 700 AC by RCT Power is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error

BESSBASE

BESSBASE is a screening intelligence platform used by asset owners, developers, and banks to assess industrial and grid-scale battery storage solutions.

  • X