Sungrow

ST255CS-2H

Industrial & Commercial AC Block

Updated Aug 27, 2026

Industrial & Commercial AC Block Updated Aug 27, 2026

Sungrow ST255CS-2H is an LFP battery energy storage system for commercial and industrial use with 257 kWh nominal energy. It is supplied as an AC block and provides 98.5% AC round-trip efficiency. The unit uses 314 Ah prismatic cells, liquid cooling, and weighs 3.2 tonnes (7,055 lb).

Use Cases

Sungrow ST255CS-2H has an energy capacity within the commercial and industrial range. It connects at 400 V, a low-voltage AC connection. Together these specifications indicate use behind the meter, inside a customer's own electrical installation.

Capabilities

Its AC block includes the inverter, which points to renewable colocation, operating alongside a wind or solar plant on one site. For Sungrow ST255CS-2H, the specifications suggest capacity value, counting as firm supply toward a network's peak needs. It holds about 2.06 h of storage at full power, calculated from 257 kWh and 125 kW.

Nominal energy

0.26 MWh

Rated AC power

0.13 MW

Round-trip efficiency (AC)

98.5 % AC

What does this system typically cost?

BESSBASE.com user price estimates for ST255CS-2H by Sungrow and similar storage systems. The ranges are LDP (Landed Duty Paid) prices per kWh that cover all expenses of delivering the goods to the buyer's premises, including production, shipping, sales margins, and import duties.

Sign up to see and submit price estimates.

BESSBASE.com users can privately compare and submit prices for ST255CS-2H by Sungrow and similar systems across 20+ international markets.

Energy & Power

Nominal energy
0.26 MWh
Rated AC power
0.13 MW
Round-trip efficiency (AC)
98.5 %

Architecture

Installation
Outdoor-capable

DC Side

Nominal DC voltage
691.2 V
DC voltage range
691.2 – 934.4 V

AC Side

AC voltage
400 V
AC voltage parameters
3P4L
AC voltage range
340 V - 440 V
Grid frequency
50 Hz / 60 Hz

Physical & Footprint

Dimensions (W × D × H)
1,150 × 1,610 × 2,450 mm
Weight
3.2 t

Battery Cells

Chemistry
LFP
Cell capacity
314 Ah
Cell format
Prismatic
Cell supplier
BYD Energy Storage

Lifespan

Protection

Ingress protection (IP)
IP55
Corrosion protection
C4 C5
Fire & safety
Combustible gas detector, Smoke detector, Heat detector, Alarm sounder, Hot aerosol fire extinguishing equipment

Full Specification Sheet

Members

The rest of this spec sheet is for members

3 more specification blocks on this product. Create a free account to see every field on every product.

You stay on this page — it fills in as soon as you are signed in.

Plant Round-Trip Efficiency

Duration
energy ÷ power 2 h
0.5C
—
State of health
new system
as-new
—
AC block (battery + PCS)
rte_ac 98.5 % @2 h
round trip @ 2 h
98.5 %
PCS (DC/AC)
Not Applicable for AC Block ESS
each way
—
—
Transformer LV/MV
typical default
each way
98.01 %
Transformer MV/HV
typical default
each way
98.01 %
Cables (all segments)
typical default
each way
98.8 %
Auxiliary power (plant's own consumption)
typical default
−4.7 pts
Plant Round-Trip Efficiency at the Point of Interconnection
88.8 %
40 % 100 %
1.126 MWh charged for every 1 MWh discharged
Both measured at the grid connection point. The plant's own power use is already included in the losses.

The calculator estimates the full "plant" round-trip efficiency (RTE) at the point of interconnection. Some values are pre-blocked depending on information on a particular ESS. The rows that are marked "each way" are one-way efficiencies; they are applied on charge and again on discharge. We then square them. To enter a bundled PCS efficiency value, use its rated-power value, not peak. If the PCS skid already includes the LV/MV transformer, set Transformer LV/MV to 100 % so those losses are not counted twice.

Site Space Required

single unit clearance 3 m / side
54.4m² total site area · 1 × 1
586 ft²0.0054 ha0.013 acres209.3 m² / MWh2,253 ft² / MWh
Unit W × D
1.15 × 1.61 m
3.77 × 5.28 ft
Site envelope
7.15 × 7.61 m
23.46 × 24.97 ft
Per unit
54.4 m²
Installed energy
0.26 MWh
1 × nameplate
Units1
Per row1
Clearance between unitsShared

Shared: one 3 m aisle serves both neighbours. Dedicated: each unit keeps its own 3 m, so gaps double to 6 m.

Clearance allowance
6m per axis · 3 m per side
19.69 ft per axis · 9.84 ft per side

Single unit — matches the stored area_sqm convention.

More Sungrow Systems

6
CompareLogoVendorSystemEnergyPowerDurationBattery CellOpen
Sungrow6.9 MWh1.8 MW AC— LFP
Sungrow5.02 MWh1.25 MW AC4 h LFP 314 Ah · Prismatic
Sungrow5.02 MWh2.5 MW AC2 h LFP 314 Ah · Prismatic
Sungrow
ST455kWh-110kW-4h AC Block · cabinet
0.46 MWh0.11 MW AC4 h LFP 280 Ah · Prismatic
Sungrow
ST255CS-2H AC Block · cabinet
0.26 MWh0.13 MW AC— LFP 314 Ah · Prismatic
Sungrow
ST225kWh-110kW-2h AC Block · cabinet
0.23 MWh0.11 MW AC2 h LFP 280 Ah · Prismatic

About the Vendor

Sungrow Tier-1 Listed Company

Sungrow Power Supply Co., Ltd., founded in 1997 by university professor Cao Renxian and based in Hefei, China, grew from a PV inverter business into a maker of grid-scale energy storage systems, shipping 10.5 GWh of BESS in 2023, 28 GWh in 2024, and 43 GWh in 2025, for 70 GWh of cumulative ESS shipments by mid-2025.

Production scale 20+ GWh
Company size Major (10000+)
Vertical integration Medium
Bankability Overall Positive

How to Read the Product Page

This profile of ST255CS-2H by Sungrow is assembled exclusively from public data to support early-stage screening and requires additional due diligence.

Always confirm these terms and technical specifications directly with the vendor and project stakeholders. Reflect all agreed-upon details in the legal agreements before making any investment decisions.

Report an error

BESSBASE

BESSBASE is a screening intelligence platform used by asset owners, developers, and banks to assess industrial and grid-scale battery storage solutions.

  • X
  • LinkedIn

© 2026 BESSBASE.com by BESSBASE LLC. All rights reserved.